Submersible pump cable 12/4 (3-wire plus ground) and 10/4 (3-wire plus ground)UL listed 3 wire copper cable (with ground) for use within the well casing supplying power to the submersible pump. p align="justify">
Sizing Table
Motor Rating
75° C Insulation - AWG Copper Wire Size
Volts
HP
KW
14
12
10
8
6
4
3
2
1
0
00
000
0000
115
1/2
.37
100
160
250
390
620
960
1190
1460
1780
2160
2630
3140
3770
230
1/2
.37
400
650
1020
1610
2510
3880
4810
5880
7170
8720
 
 
 
3/4
.55
300
480
760
1200
1870
2890
3580
4370
5330
6470
7870
9380
 
1
.75
250
400
630
990
1540
2380
2960
3610
4410
5360
6520
7800
9350
1-1/2
1.1
190
310
480
770
1200
1870
2320
2850
3500
4280
5240
6300
7620
2
1.5
150
250
390
620
970
1530
1910
2360
2930
3620
4480
5470
6700
3
2.2
120
190
300
470
750
1190
1490
1850
2320
2890
3610
4470
5550
5
3.7
 
110
180
280
450
710
890
1110
1390
1740
2170
2680
3330
7.5
5.5
 
 
 
160
250
390
490
600
750
930
1160
1430
1760
15
11
 
 
 
 
170
270
340
430
530
660
820
1020
1260
Kalas Submersible Cable 12/3 With Ground 100' # KAL-ACC-KAL100-12 (C)
Kalas flat parallel PVC insulated THW submersible pump cable with ground. AWG 12, with 3 conductors plus ground, 7 strands, 0.0305" diameter strands per cable, 0.045" insulation thickness and 14 lbs weight Requires splicing to motor leads. $89.00
Kalas Submersible Cable 12/3 With Ground 200' # KAL-ACC-KAL200-12 (C))
Kalas flat parallel PVC insulated THW submersible pump cable with ground. AWG 12, with 3 conductors plus ground, 7 0.0305' diameter strands per cable, 0.045" insulation thickness and 28 lbs weight. Requires splicing to motor leads. $178.00
Kalas Submersible Cable 10/3 With Ground 100' # KAL-ACC-KAL100-10 (C)
Kalas flat parallel PVC insulated THW submersible pump cable with ground. AWG 10, with 3 conductors plus ground, 7 stands 0.0385" diameter strands per cable, 0.045" insulation thickness and 20 lbs weight Requires splicing to motor leads. $146.00
Kalas Submersible Cable #10/3 With Ground 200' KAL-ACC-KAL200-10 (C)
Kalas flat parallel PVC insulated THW submersible pump cable with ground. AWG 12, with 3 conductors plus ground, 7 strans 0.0385" diameter strands per cable, 0.045" insulation thickness and 40 lbs weight. Requires splicing to motor leads. $292.00
These 4 wire, black, heavy wall heat shrink splicing kits can be shrunk over a large diameter connector and still effectively seals watertight to a small diameter cable. Four butt connenctors are included.Slip shrink tube on each wire, crimp connector on each wire, center tubing over connector and heat from center outward, splice is complete when sealant flows fron end of tube. Do not overheat
The tape method was the only way to make a good splice until shrink tube splice kits became available. Many installers still use tape because it has worked for them for years. You crimp the conductors together, wrap each conductor with a layer of rubber tape followed with a layer of plastic electrical tape. This makes a watertight connection and insulates the conductors from each other and the well casing. Properly done, this technique makes an excellent splice, but is very time consuming.