Duplex 3Ø Control Panel 2.5 to 4.0 Amp Range # BF3BD-D740-25-40. Duplex waterproof control panels with hand-off-auto switches, running lights, (H-O-A) elapse time meters for each pump plus a visual flashing high water alarm, and a pulsating high water alarm horn with silence button in a Nema 4X water-proof fiberglass enclosure for a variety of sump, effluent, sewage and water transfer applications.
Specifications
NEMA 4X fiberglass enclosure with gasketed hinged door and stainless steel hardware and lockable latch.
Application: Superior quality duplex level controller for a variety of sump, effluent, sewage and water transfer applications.
Three Level Floats Operation:
Float #1: Both pumps off; Float #2: Lead pump on; Float #3: Lag pump and visual & audio alarms on.
Four Level Floats Operations:
Float #1: Both pumps off; Float #2: Lead pump on; Float #3: Lag pump on. Float #4: Visual & audio alarms on.
Exterior Mounted Components:
Elapsed time meters for each pump; Running lights for each pump; Silence switch for manual silence of alarm horn; Alarm test switch for tested alarm circuit; Red high intensity manual reset alarm light (top mounted); Pulsating, corrosion proof 30 Watt, 95 dB. automatic reset alarm horn.
Interior Mounted Components: Magnetic contactors; Adjustable motor protectors (3 phase controls only) 115 volts control transformer (3 phase controls only); Toggle switches mounting plate: H-O-A (Hand-Off-Auto)switch for each pump; On-off control circuit switch; Electronic control board: Solid state pump alternator displays float status; Alternator selector switch. Choice of alternation or only one pump operation; Lag pump 5 second lag start relay; Auxiliary alarm contacts provided for remote control connection; Color coded wiring, screw type terminals and plug-in sockets
Three Phase Power Feed:
Field adjustable for 208/230/460/575 Volts 60 Hz
Note: Panel can be wired for a single power feed and control circuit or it can be wired to a separate power supply to insure alarm integrity in case of a tripped main breaker.
Documentation
Field wiring diagram; Panel schematic; Installation instructions.
Certifications
Entire unit is UL and cUL listed
Duplex Control Panel Horsepower Rating
Model
Amperes
Volts 208 3Ø
Volts 230 3Ø
Volts 460 3Ø
BF3BB-D740-25-40
2.5-4.0
-
3/4
1
Ampere draw from the pump nameplate must be used to size the panel correctly.
Controls are factory wired for 3 float operation.
They are field modifiable for 4 float operation.
Float switches are not included and are sold separately